UC Davis models chillerless cooling for a modular datacenter

In this article
THE QUICK TAKE

The reported cooling-power ratio is a modeled operating point; it does not establish a measured datacenter PUE or commercial system performance.

Researchers at the University of California, Davis Western Cooling Efficiency Center (WCEC) investigated removing heat from a compact modular datacenter without a compressor chiller. In the proposed arrangement, liquid passes through chip cold plates and rejects heat to outdoor air through a dry cooler. At 40 °C ambient air and a 75 °C GPU case-temperature limit, the model predicted cooling power equivalent to 2.1% of compute power. The center announced the study on May 22, 2026.

This is a system calculation, rather than an operating datacenter result. The authors also tested individual component characteristics experimentally, but available published information does not establish a full-system field measurement of that 2.1%. The work by Ines-Noelly Tano, Erfan Rasouli, and Vinod Narayanan appears in the Journal of Electronic Packaging: see the paper DOI.

From the chip to outdoor air

The design targets a modular datacenter with high compute-equipment density. The abstract specifies 20 kW of compute power per cubic meter. A mixture of water and 25% propylene glycol circulates through one loop, collecting chip heat through MUSE cold plates and carrying it to a counterflow microchannel polymer heat exchanger, or MPHX, dry cooler. The cooler transfers that heat to ambient air. See the research abstract.

A cold plate is a heat exchanger attached to a hot component. MUSE divides flow into parallel paths, while microscopic pin fins increase heat-transfer surface area. The abstract specifies a pin-height-to-characteristic-width ratio of 7.3:1 and fabrication by electrochemical additive manufacturing. This supports intensive heat transfer into liquid, but circulation still needs energy: channel resistance and liquid flow affect required pump power.

The dry cooler completes the chain. Fans move outside air through its heat exchanger, while the modeled arrangement avoids a compressor chiller. That does not eliminate cooling energy consumption. A dry heat exchanger also needs a temperature difference between coolant and ambient air. Hotter outdoor conditions make it harder to maintain allowable chip temperatures without increasing exchanger area or air and liquid flow. ASHRAE describes warm-liquid cooling as a route to dry coolers and notes the risk of hardware throttling outside their thermal limits.

What 2.1% and below 1% mean

For the modeled point of 40 °C outdoors and 75 °C at the GPU case, the researchers optimized liquid and airflow rates. The abstract additionally specifies heat flux of 74 W/cm². Under those conditions, predicted cooling power was 2.1% of compute power. This ratio characterizes the selected configuration and operating point, rather than universal liquid-cooling efficiency. See WCEC and the abstract.

The center also reports modeled variants below 1%. Those calculations improve the thermal interface between chip and cold plate and improve the dry cooler. The figure belongs to those improved scenarios, rather than the baseline configuration or a measured installation. The available summary does not specify all required improvements or establish that commercial equipment achieves them simultaneously.

Available materials also do not fully disclose the numerator and denominator boundaries: for example, which auxiliary loads count as cooling power and exactly which electrical loads are included in compute power. Consequently, 2.1% cannot directly be converted into whole-facility PUE or treated as the fraction of all datacenter electricity. PUE relates facility energy consumption to IT-equipment consumption and includes a broader collection of loads.

The publisher’s full paper was unavailable during this review: the DOI page did not open through the research tool. Detailed methodology, uncertainty, and the composition of measured components therefore could not be checked in the primary full publication. The WCEC news and research abstract originate from one research group and are not independent replication.

Where the idea could help

The arrangement is relevant to modular and edge datacenter designers fitting substantial compute into limited space and able to use sufficiently warm coolant. Direct heat removal brings cooling close to the main heat sources; a dry cooler rejects that heat outdoors without a chiller. This direction is consistent with general liquid-cooling principles described by the US Department of Energy.

A practical project still needs to establish cold-plate compatibility with the selected processors, cooling of other components, operation in local weather, redundancy, and servicing. Economics cannot be derived from the power percentage alone: heat exchanger and pump cost, installation area, and load profile also matter. The study currently identifies a promising component combination and conditions under which a model predicts low cooling power. Independent confirmation of the same system’s reported figures was not established.

For practical interpretation, see the difference between rated, commanded, and observed flow and electricity and cooling cost boundaries: a modeled point cannot replace observation of the complete installation.