The capacity and protection numbers are requirements at named interfaces; an actual installation needs its own configuration and acceptance evidence.
Diablo 400 describes a disaggregated rack-power architecture and its interfaces. Its capacity numbers are requirements for a designed system, rather than measurements of a universally available rack product. The most useful reading connects the power bus, outgoing cable, protection and receiving converter instead of treating the largest wattage as a standalone deployment result.
Identify the document revision
The 0.5.2 base specification is effective May 30, 2025. A later 0.7.0 specification, effective March 1, 2026, updates telemetry and connector material, among other revisions. It retains the core bus and cable requirements discussed here.
Keeping both identities prevents an early requirement from being presented as the latest unchanging wording. A document revision is also distinct from an implemented product revision or a commissioned installation. None of those milestones should be inferred from the existence of an open specification.
Read bus capacity at its own boundary
The design calls for a vertical three-conductor bus distributing +400 V, common and −400 V, supporting up to 1.1 MW average load power. This is the specified distribution-bus design capacity, not a guarantee that every attached IT rack receives that power.
Source conversion, energy storage, branch protection and downstream loads remain separate building blocks. Their limits and redundancy can differ. A large upstream bus rating cannot substitute for the capacity of one outgoing connection or the receiving conversion stage.
Cable ratings include control behavior
The specified outgoing connections range from 63 A/50 kW to 125 A/100 kW per cable. The text requires individually current-limited outputs and latching/interlock behavior that turns off source and load power before disengagement. The voltage-drop budget is 0.1% over 5 m.
These statements describe required interface behavior and a design budget. They are not a field measurement of a particular cable’s loss or a blanket approval of interchangeable connectors. Matching the nominal voltage alone leaves protection, signaling and mechanical compatibility unresolved.
The later document also adds connector appendices and labels connector part numbers preliminary. Thus even detailed tables need their stated maturity preserved. A reader should not silently promote a listed option into a universally finalized interconnect.
Keep specifications separate from acceptance evidence
For an equipment inventory, map the particular source, distribution branch and receiver to the exact adopted specification. Record rated continuous load and the intended redundancy case independently of any short-duration peak allowance. Preserve which documents supply requirements and which tests demonstrate an actual assembly meeting them.
The site power budget guide explains why an installation’s usable allowance comes from its real boundary. The power measurement guide explains why input, converter output and IT-load readings cannot be substituted for one another.
Diablo 400 contributes a concrete interface and protection contract for high-density power distribution. It does not supply observed GPU availability, an efficiency measurement for a complete site or proof that a named installation has passed acceptance. Those conclusions require evidence about the implemented system beyond the specification’s capacity targets.