H100 liquid cooling: what a two-server comparison actually measured

In this article
THE QUICK TAKE

The liquid-cooled server used less node power, but training runtime differences were smaller than the stress-test headline and platform differences limit causal claims.

Two servers with the same number of NVIDIA H100 GPUs can differ substantially in temperature and power under load. In a research team’s comparison, direct liquid cooling produced GPU temperatures of 41–50 °C in a stress test, versus 54–72 °C with air cooling. Average GPU Burn performance was 54 versus 46 teraflops per GPU, approximately a 17% difference. However, language-model fine-tuning showed much smaller runtime differences, and the servers differed in more than their cooling. See the open research paper.

The work, Cooling Matters, appeared in IEEE Transactions on Cloud Computing. The Lawrence Berkeley National Laboratory publication record gives June 8, 2026; the arXiv preprint first appeared on July 22, 2025. IEEE Xplore required a browser verification challenge during source review, so experimental details below were checked against the open preprint, and the journal date against LBNL’s record.

Which systems were compared

The authors studied two HGX nodes, each with eight H100 GPUs carrying 80 GB HBM3 each. Both had 1.5 TB RAM, but different CPUs: the liquid-cooled node used a 48-core AMD EPYC 9474F, while the air-cooled node used a 64-core EPYC 9534. Server model names are not provided in the experimental description. See the method and configuration.

For context, NVIDIA’s Hopper architecture description specifies 80 GB HBM3 for H100 SXM5. That is a manufacturer specification, rather than independent measurement of the studied servers; the paper does not identify their precise GPU form factor.

In the liquid-cooled system, cold plates removed heat directly from CPUs and GPUs through a closed coolant loop, while memory and storage remained air cooled. This reduces the heat that case airflow must remove, but does not eliminate fans or external heat rejection. The liquid server had four fans; the air server had eight. The air-cooled node additionally used a rear-door rack heat exchanger. Both depended on shared chilled-water infrastructure at 20 °C, with room temperature at 21–22 °C. See the test setup.

This distinction matters: the study compares two complete real configurations, rather than one server before and after a cooling replacement. Different CPUs, fans and heat-removal paths can influence the result.

Stress testing and training are different workloads

GPU Burn put all eight accelerators in each node under an intensive synthetic workload for two hours. The authors report double-precision computation, performance taken from the program itself, and node power polled through IPMI every 20 seconds. Alongside the temperatures and average 54 versus 46 TFLOPS per GPU, they report average loaded-node power of 6.99 kW for liquid cooling and 8.16 kW for air cooling. See the GPU Burn results.

That 17% concerns a specific stress test, rather than every application or neural-network training. The authors connect the difference to temperature, but the experiment does not isolate cooling from other platform characteristics or prove that thermal throttling caused the entire gap. Its stress-test result also cannot be compared directly with H100’s specified peak performance for other operation types.

The practical portion fine-tuned five language models from Mistral-7B to Qwen2.5-32B on Alpaca. Training used eight GPUs, distributed execution and QLoRA; each model ran for one epoch with effective batch size 32. Mistral-7B, for example, took 2702 seconds on the liquid-cooled server and 2721 seconds on the air-cooled server, approximately a 0.7% difference. Average complete-node power was 5051 and 6135 W respectively. Qwen2.5-32B took 9738 and 9783 seconds. These are particular fine-tuning runs, rather than training a model from scratch. See table I and conditions.

The researchers also trained three vision-language models on UCF101. Runtime differences depended on the task: EVL took 14 530 seconds with liquid cooling and 15 296 seconds with air cooling, about 5%; ViTA-CLIP took 91 654 and 91 941 seconds, about 0.3%. Average node-power differences also varied substantially, at 391 W and 1508 W for those two models respectively. Even within this paper, one universal improvement figure would be misleading. See tables II–III.

What the numbers mean for data centers

Lower server temperatures and power are relevant to dense GPU-rack operators, cluster owners and teams planning training. Reducing thermal resistance between a hot component and coolant can provide more temperature headroom. If temperature constrains chip frequency, this may help sustain performance; the size of that effect needs measurement on the actual configuration and workload.

Node-level power does not measure the whole data center’s electricity. Pumps, liquid distribution, chillers, heat exchangers and outdoor conditions can change the picture. The paper’s figures do not establish annual PUE or task-energy savings including all supporting infrastructure. LBNL separately notes that embedded server fans can affect cooling-efficiency comparisons. See the laboratory explanation.

The work is useful as a measured comparison, but should not be described as independent reproduction of another test: an author represents Johnson Controls, LBNL and other scientific organizations participated, and the laboratory describes collaboration with hardware manufacturers. Only one node of each type was compared, making variation between units and repeated runs difficult to assess from the published results. See the authors and hardware and LBNL project context.

A procurement decision should request tests of candidate servers on the intended tasks: runtime, node energy and cooling-infrastructure energy separately, coolant and room temperatures, and repeated runs. The study demonstrates possible differences; it does not guarantee the improvement at a particular facility.

Sources

For interpreting operating costs, see power-measurement boundaries and power and cooling conditions.