In this article
Accuracy is a percent error, while ReadingAccuracy follows ReadingUnits; renaming the field without changing interpretation manufactures a different measurement claim.
A collector migration renames Accuracy to ReadingAccuracy while keeping the same numeric interpretation. Its dashboard still looks plausible, but the interval around each reading has changed meaning. Review the unit contract explicitly before using the migrated result to decide whether a facility measurement distinguishes acceptable operation from a limit.
Preserve both schema meanings
The DMTF Sensor schema defines deprecated Accuracy as estimated percent error of measured versus actual values. ReadingAccuracy instead gives an absolute maximum deviation in the sensor’s ReadingUnits. They are not interchangeable labels for an unqualified number. Keep the returned schema version and original field beside normalized output. The sensor interpretation guide establishes the surrounding value, validity and physical-context record needed before either accuracy field is useful.
Build a bounded conversion fixture
Use an artificial scalar reading of 100 W and an accuracy value of 2. Interpreting the old field as percent gives an illustrative deviation of 2 W at that reading; the newer field states 2 W directly. Their accidental equality hides the migration error. Change the constructed reading to 50 W: the percentage interpretation gives 1 W, while an absolute ReadingAccuracy of 2 still denotes 2 W. These are parser examples, not instrument calibration results.
Keep precision out of the conversion
The schema separately defines Precision as significant digits. More displayed digits do not create a narrower maximum deviation, and rounding a reading does not establish the instrument’s physical accuracy. Preserve these fields separately in export and storage. Do not infer a missing accuracy value from decimal places or from a nearby sensor with the same unit. The supported representation may differ across devices, even when their dashboard labels look identical.
Do not invent statistical confidence
NIST uncertainty guidance distinguishes measurement error from uncertainty and explains that an uncertainty evaluation can contain several components. A schema field describing maximum deviation does not itself provide a probability distribution, coverage factor or complete calibration history. Do not present its interval as a statistical confidence statement without additional evidence. Retain the manufacturer’s conditions and any separate calibration record when the decision actually requires a defensible uncertainty budget.
Test the migration near a boundary
Exercise percent-only, absolute-only, absent and inconsistent fixtures. Verify units survive normalization and that missing evidence remains unknown. For a decision close to a threshold, report whether the applicable measurement evidence can resolve the difference rather than forcing a pass from the central value. The time-alignment guide adds another independent requirement: readings compared across an event must cover meaningful acquisition intervals, even when their accuracy metadata is interpreted correctly.
Accept the semantic change deliberately
Acceptance requires preserved raw fields, an explicit conversion policy and tests that separate percentage from absolute behavior. Flag unsupported combinations instead of silently choosing whichever interval looks smaller. Revisit downstream alerts and historical comparisons if the earlier collector misinterpreted the field. This review establishes what the management data claims; it does not recalibrate the sensor, guarantee an operating limit or make uncertainty disappear by changing the number of digits shown on a dashboard.