PSU efficiency ratings: keep load points separate from measured wall power

In this article
THE QUICK TAKE

Redfish PowerSupply EfficiencyRatings pairs EfficiencyPercent with LoadPercent. The efficiency is rated at the specified electrical load. Dropping the load coordinate changes the meaning of the value before any system calculation begins.

A capacity report selects the highest efficiency percentage in a PSU inventory and applies it to every load level. The reported efficiency array contains ratings at specified load points. It is not a continuous measurement of the node’s current wall-power conversion efficiency.

The hardware contract

Redfish PowerSupply EfficiencyRatings pairs EfficiencyPercent with LoadPercent. The efficiency is rated at the specified electrical load. Dropping the load coordinate changes the meaning of the value before any system calculation begins.

Keep the rating as a structured pair associated with the supply identity. Multiple entries do not represent simultaneous measured samples to average indiscriminately. Missing load or efficiency values remain incomplete ratings rather than permission to reuse the best value from another entry or another power-supply model.

Implementation details

Separate rated characteristics, a planning estimate and measured operation. If an estimate interpolates between rated points, state the method and the conditions assumed; the inventory does not independently validate that interpolation for the deployed system.

A complete node can contain several supplies with a particular load-sharing or standby configuration. The total AC input and delivered DC output need their own measured boundaries before a whole-node efficiency is claimed. This article does not change power policy or run an electrical test. Its review preserves the source rating coordinates and prevents a convenient catalog percentage from becoming an asserted measurement of current infrastructure energy cost or usable capacity.

A constructed acceptance test

Build a fixture with several efficiency/load pairs and an operating point that does not exactly match any rating. The report must display the source pairs and label any derived estimate explicitly. It must not select the maximum percentage as a universal constant.

Add incomplete entries and a replacement supply with a different curve but the same rated output capacity. Verify that the baseline records the changed characteristics. Compare a separate measured input/output fixture without replacing it by catalog data when the measurement is unavailable. The acceptance evidence should identify whether each displayed number is a rating, an assumption-based estimate or an actual observation, including its device and load context.

Recovery and limits

Correctly preserving load points does not certify energy performance under an inference workload. Measure the actual system boundary when that claim matters, retaining the selected power configuration and useful work. A replacement can change the rated curve without proving that operating cost improved or worsened. Keep those conclusions separate and preserve uncertainty. The inventory should support a transparent comparison, not turn one favorable rating into a guarantee about every operating point of a GPU server.

Primary references

DMTF Redfish PowerSupply; Redfish Protocol.

This is a proposed acceptance procedure, not an executed Retrivium test. Preserve the observed implementation version and unresolved outcomes; the documentation does not certify a particular device or establish its remaining service life.