Preserve circuit and phase scope, source references and units before aggregation; duplicate sensor views do not represent additional consumption.
A collector adds a circuit’s current field to its phase-current entries and reports more load than the PDU observed. Redfish can expose overlapping views of the same sensor. Preserve circuit scope, wiring representation and source identity before aggregation. The task is interpreting management data, not calculating permission to connect equipment or changing an electrical arrangement.
Locate the circuit resource
Identify whether the resource represents mains, a branch or another circuit boundary. Preserve the management service and its relationship to the equipment inventory. A rack-wide value and a branch value can include the same consumers. Administrative names are insufficient to establish independence, and user-assigned consumer strings are descriptive metadata rather than verified electrical topology.
Read the wiring representation
PhaseWiringType and ElectricalContext describe how the circuit and conductors are represented. The schema constrains when a single current or voltage field is appropriate and provides phase-aware readings for other configurations. Keep the actual supported representation rather than forcing every circuit into one flat current column. Unknown context must remain unknown instead of being assigned a convenient single-phase interpretation.
Detect overlapping sensor views
The documented phase-current representation can duplicate a sensor also referenced by the simpler current field for applicable circuits. Compare source references and context before summing. A duplicate view is not additional consumption. Likewise, currents from different conductors cannot be added and labeled total real power merely because every value is numeric; the units and measured quantity must retain their physical meaning.
Preserve acquisition and validity
Use the associated sensor’s units, reading time and unavailable-value behavior. Fetching several resources together does not prove simultaneous acquisition. Do not substitute zero for a missing phase or combine fresh and stale observations into an apparently precise total. Resource health and breaker state also answer different questions from the measured current at a particular observation boundary.
Verify the collector contract
Exercise a synthetic circuit with overlapping references, missing phase data and distinct branch and mains views. Confirm that the report preserves scope and avoids duplicate addition. A useful output explains what each reading covers and which aggregation is supported. It does not establish an electrical operating limit, certify redundancy or convert one management snapshot into a complete energy account for the inference site.
Primary references
DMTF Redfish Circuit Phase and Sensor Scope.
DMTF Redfish Resource Status and Health.
Related reading: GPU Colocation Power Budget: Check the Site Limit; Dual PSUs: accounting for A/B inputs and redundancy.