﻿# Turkcell cooling-water recovery: what the reported percentages mean

Turkcell reports wastewater recovery and a lower reject ratio. Their denominators, reporting history and corporate boundaries determine the practical meaning.

Author: Retrivium editorial team
Updated: 2026-11-05
Canonical URL: https://retrivium.ai/journal/turkcell-data-centre-wastewater-recovery-denominators/
Language: en

Turkcell's water-recovery disclosure is a concrete operating case, but its percentages describe process streams. They are not a direct measure of water per AI request or a universal reduction in data-centre water withdrawal. Reading the denominator correctly is more useful than combining the reported percentages into a single efficiency headline.

## What the operator actually reports

The [2025 integrated annual report](https://ffo3gv1cf3ir.merlincdn.net/SiteAssets/Hakkimizda/dokuman/pdf/trkcll-efr-en-2025-final.pdf?20260316_03=) says reverse-osmosis systems at the Izmir and Gebze data centres recover 60% of wastewater generated there. Recovered water is reused in cooling. It separately reports that improvements at Ankara reduced the wastewater ratio from 40% to 16%.

These statements concern different locations and quantities. The recovery share is not the fraction of all facility intake that is recycled, and the Ankara ratio is not automatically the same denominator as the recovery measure elsewhere. The passage supplies no site-level flow series that would let a reader reconstruct both calculations independently.

## The result was already disclosed before this reporting year

The [2024 integrated report](https://ffo3gv1cf3ir.merlincdn.net/SiteAssets/Hakkimizda/dokuman/pdf/Trkcll-efr-en-2024-Final.pdf?20250916_03=), in its water and data-centre efficiency discussion, already reports the same recovery share and completed Ankara improvement. The later report therefore should not be read as evidence that installation occurred for the first time during the later reporting year.

Repeated disclosure can preserve an operating result without documenting a newly measured annual improvement. A historical comparison needs a commissioning date and matching periods before attributing a step change to a particular year. Neither date is established merely by the cover year of an annual report.

## A ratio change is not an absolute volume saving

The change from 40% to 16% is a reduction of 24 percentage points. Its relative reduction is 60%, calculated from those ratios. That arithmetic does not establish a 60% reduction in total water use: the underlying process flow may also change.

For example, a larger cooling operation could recover a higher fraction while using more water in total. This is a boundary illustration, not an observation about Turkcell's facilities. Absolute volumes and a consistent denominator are needed to distinguish resource efficiency from changes in the scale of operations.

## Separate corporate water from cooling water

The later report describes identifying data-centre consumption points, adding measurement infrastructure and separating domestic and process uses. It also says much of corporate water use serves employees' daily needs. Corporate totals therefore cannot simply be assigned to the data centres, let alone to a model workload.

The reviewed passage is an operator disclosure; we did not inspect facility meters or independently verify its process ratios. That is narrower than asserting that every sustainability indicator in the report lacks assurance. A claim about independent verification requires the relevant assurance scope, rather than the presence or absence of an audit elsewhere in a corporate report.

## What would support a workload-level interpretation

A useful follow-up record would retain intake, recovered flow, final discharge, time interval and the site boundary, with process and domestic uses separated. Relating water to IT activity additionally requires an appropriate workload or energy denominator.

The [energy measurement guide](/journal/measuring-energy-per-inference/) explains related boundary discipline, while [power and cooling](/journal/power-and-cooling/) provides operating context. Turkcell's example supports a specific water-reuse account. It does not supply a portable water coefficient for an unrelated GPU server or prove how much water an individual inference saved.